Evant ISD - Main Campus - 1937 Gym
- Year Built1937
- Square Footage9,272
- Replacement Cost$7,219,938
- Condition Budget$2,622,133
- Facility Condition Index42%
Condition Assessment
System Rating ScoreGood
Fair
(or will require attention in near future 3-10 years)
Poor
(or will require attention now 0-2 years)
Exterior
Poor
Exterior Structure: Repair cracking in exterior masonry walls.
Good
Foundation: No issues observed.
Poor
Parking/Traffic: Information on Main Building Dashboard.
Fair
Site: Information on Main Building Dashboard.
Poor
Doors: Replace all wood exterior doors with metal. Replace all exterior metal doors and frames. Replace wood doors and frames and all door hardware that is not ADA compliant.
Fair
Exterior/Interior Windows: Replace calking around window units.
Fair
Roof: Roof systems on the 1937 Gym were installed in 2000 and are in overall fair condition. Manufacturer-recommended maintenance should be implemented to maintain the integrity of the systems.
Interior
Fair
Interior Structure: Replace damaged wood flooring components. Replace wooden staircase and handrails. Repair damaged masonry surfaces and paint. Replace damaged wallboard surfaces. Replace wood paneling surfaces. Replace vinyl wallboard paneling. Replace all ceiling tiles and grid systems. Paint all visible structural components on the ceiling.
Poor
ADA: Campus lacks accessible routes into and around the facility. No ADA compliant restrooms or seating.
Poor
Furnishing, Fixtures, Equipment: Replace all stage lighting and equipment. Replace all restrooms stalls and accessories. Replace bleachers for functionality and ADA compliance. Replace damaged moveable furnishings as needed.
Poor
Electrical: Mechanical systems 30 years or older should be inspected and repaired or replaced as inspection dictates. Install LED lighting. Install data system. Incorporate facility into central communication system. See Safety & Security recommendations on the Facility Details page. Install lighting control system.
Poor
Safety/Security: See Safety & Security recommendations on the Facility Details page.
Fair
Flooring: Replace all carpeted flooring. Patch cracks in concrete flooring and seal. Replace damaged and missing ceramic floor tiles and deteriorated grout.
Priority Projects
- Repair cracking in exterior masonry walls.
- Replace all plumbing fixtures.
- Replace calking and missing fasteners on roof system.
- Perform manufacturer-recommended maintenance.
- Replace all restrooms stalls and accessories.
- Replace all wood exterior doors with metal.
- Replace all exterior metal doors and frames.
- Replace wood doors and frames and all door hardware that is not ADA compliant.
Additional Projects, if Funds Become Available
- Install gutters and downspouts.
- Structural evaluation.
- Retention wall repairs.
- Install HVAC system.
- Grade exterior for drainage.
- Replace damaged wood flooring components.
- Replace wooden staircase and handrails.
- Repair damaged masonry surfaces and paint.
- Replace damaged wallboard surfaces.
- Replace wood paneling surfaces.
- Replace vinyl wallboard paneling.
- Replace all ceiling tiles and grid systems.
- Paint all visible structural components on the ceiling.
- Plumbing systems over 30 year of age should be inspected closely and considered for replacement.
- Replace all stage lighting and equipment.
- Replace bleachers for functionality and ADA compliance.
- Replace damaged moveable furnishings as needed.
- Mechanical systems 30 years or older should be inspected and repaired or replaced as inspection dictates.
- Install LED lighting.
- Install data system.
- Incorporate facility into central communication system.
- See Safety & Security recommendations on the Facility Details page.
- Install lighting control system.
- Replace calking around window units.
- Replace all carpeted flooring.
- Patch cracks in concrete flooring and seal.
- Replace damaged and missing ceramic floor tiles and deteriorated grout.
- Install gutters and downspouts.
- Structural evaluation.
- Retention wall repairs.
- Install HVAC system.
- Grade exterior for drainage.
Educational Adequacy Assessment
System Rating ScoreAdequate Spaces
Needs Improvement
Not Adequate
Poor
Visual and Performing Arts: Stage doesn't meet UIL standards and all adjacent stage systems need replacement. Facility needs updating for ADA compliance, security, storage, furnishings, internal and external finishes.
Poor
Security: See Safety & Security recommendations on the Facility Details page.
Poor
Physical Education: Gym in fair condition but facility lacks restroom facilities and doesn’t meet ADA standards.
Actions to Improve the Educational Environment
The 1937 Gym is currently being used for after school theater programs and some physical education classes. The facility lacks restroom facilities and accessible features and updates should be made to cater to the educational programs being offered there.